Pre/post-download parameter consistency verification is a very import task in the operation and maintenance of DCS in nuclear power plant. The conventional manual verification approach suffers from heavy workload, long duration, and risks of missing items, data misalignment, and misjudgment. This paper proposes a method for automatic extraction of control station algorithm lists and online parameter verification. The method parses control station configuration project files to automatically filter algorithm blocks according to user-specified block names and database types, and generates standardized list files containing Dynamic Data Exchange (DDE)-compliant parameter reading expressions. Online parameters are batch-read and compared via the DDE interface before and after program download based on the same list file, guaranteeing one-to-one correspondence between the two acquisitions. Engineering application on CPR1000 nuclear power plants shows that the proposed method significantly reduces manual effort and improves the efficiency, accuracy, and reliability of parameter verification.

Downloads

Download data is not yet available.

References

[1] Wang, C., & Luo, A. (2010). Design and application examples of distributed control systems (DCS) (2nd ed.). Publishing House of Electronics Industry.

[2] International Atomic Energy Agency. (2016). Design of instrumentation and control systems for nuclear power plants: IAEA safety standards series No. SSG 39. IAEA.

[3] International Electrotechnical Commission. (2011). IEC 61513:2011 Nuclear power plants Instrumentation and control for systems important to safety General requirements for systems. IEC.

[4] International Electrotechnical Commission. (2013). IEC 61131 3:2013 Programmable controllers Part 3: Programming languages. IEC.

[5] Microsoft. (2019, August 24). Dynamic data exchange. https://learn.microsoft.com/en us/windows/win32/dataxchg/dynamic data exchange

[6] OPC Foundation. (2003). OPC data access custom interface standard, Version 3.00. OPC Foundation.

[7] 3S Smart Software Solutions GmbH. (n.d.). CODESYS development system documentation. https://www.codesys.com/

[8] Python Software Foundation. (2026, November 13). Python 3 documentation. https://docs.python.org/3/

[9] Microsoft. (2022, July 12). Excel VBA reference. https://learn.microsoft.com/en us/office/vba/api/overview/excel

[10] HollySys Group. (n.d.). HOLLiAS MACS distributed control system technical manual. HollySys Group.

Downloads

Published

2026-11-15

Issue

Section

Articles

How to Cite

Kang, Z. (2026). Automatic Parameter Extraction and Verification Method for Nuclear Power Plant DCS Control Stations. International Core Journal of Engineering, 12(11), 65-72. https://doi.org/10.6919/ICJE.202611_12(11).0007